Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/03/2000 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection 0000* OK TO CLEAR |
|
| 11/02/2000 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection 0245* REMOVE GROUNDING ELECTRODE CONDUCTOR FROM NEIGHORS PROPERTY AND INSTALL ON THIS OWNER PROPERTY IT IS INSTALLED ON NEIGHBORS WOOD SHED (LIGHTING MAY DAMAGE) FEEDER TO SUB PANEL IN STORAGE ROOM SHOULD BE INSTALLED IN CONDUIT TO PROTECT FROM PHYSICAL DAMAGE NEC 300-4 336-6-B |
|
| 11/01/2000 | ELECTRIC - SERVICE RELOCATION | Denied | NEED A NEUTRAL CONDUCTOR AT SUB PANEL GROUND RODS MUST BE WITHIN PROPERTY BOUNDARIES NEED GAS BOND WILL NEED A PERMANENT ADDRESS TAG ENGRAVED OR RAISED LETTER MUST USE 1/4" HARDWARE FOR PANEL AND RISER, NEED A GREATER ANGLE FOR RISER SUPPORT |