Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* THE FOLLOWING REPAIRS/ CORRECTIONS MUST BE DONE TO THE ELECTRIC SERVICE 1. THE MAIN LOAD PANEL MUST BE SECURED TO THE WALL 2. THE 3" ROUND JUNCTION BOXES MUST BE COVERED 3. A SET OF TWO GROUND RODS SET 6' APART AND A GROUND WIRE RUN FROM PANEL TO GROUND. RODS AND TO GAS LINE |