Permit: T00EL02506

Parcel: 125073360


Addresses:

431 N PLUMER AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/01/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
OK TO CLEAR
10/26/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
BOND BUSHINGS OR GROUNDING LOCKNUTS REQUIRED ON ALL SERVICE RELOATED ENCLOSURES DISC SWITCH J-BOX LOAD CENTER
ID GROUNDING CONDUJCTORS 200-6 NEC
SPLIT BOLT NOT APPROVED FOR MULTIPLE WIRE SPLICES 110-3B NEC (J-BOX)
INSTALL MECH LUGS OR GROUND BAR
SELF TAPPOING SCREWS NOT ALLOWED TO ATTACH MECH LUGS FOR GROUND IN DISC SW 250-8
INSTALL EQUIP GROUND IN GUTTER OR BOND TO GUTTER 370-40-C NEC
ID DISC SW (LABEL) 110-22 NEC
GAS PIPING SYSTEM MUST BE BONDED 250-104B