Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/23/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) ROMEX MUST BE PROPERLY TERMINATED INTO PANCAKE BOX, ONLY 1 14/2 ALLOWED PER CODE SEE 370-4, 370-17, 370-16A. 2.) BOXES TOBE GROUNDED 250-148, 370-4 NEC. 3.) ELECTRICAL TAPE NOT APPROVED. 4.) FOR SPLICES ON BRANCH CIRCUITS, USE LISTED WIRE NUTS OR OTHER APPROVED METHOD. 110-3,110-12,90-4 NEC. |
| 09/12/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*NOTES 1.) NEED J-BOXES BEHIND FIXTURES. |
| 09/11/2001 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*KNOCKED ON DOOR, NO ANSWER. NOT SURE WHICH LIGHT FIXTURES TO INSPECT, NO PLANS. |