Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2001 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection 0000*INSTALL FIXTURE MUST COVER ENTIRE PANCAKE BOX. | |
| 04/11/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) UNDER GROUND OK 2) MUST SEE LIGHT FIXTURE BOX TYPE ON WALLS, AND UNDER GROUND WIRING MUST BE GFCI PROTECTED |
|
| 03/27/2001 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* 1) TYPE OF DIRECT BURIAL OK AT 12" DEPTH BUT MUST BE GFCI PROTECTED | |
| 03/06/2001 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* NOTES: TYPE UF CABLE MUST BE 24" MINIMUM BELOW GRADE. INSTALL J BOX AT FIXTURE LOCATIONS ON WALL UNLESS LIGHT FIXTURE IS LISTED FOR WIRE TERMINATION WITHIN. LIGHT FIXTURES TO COMPLY WITH CITY OF TUCSON OUTSIDE LIGHTING ORDINANCE. 50 WATTS MAX UNLESS SHIELDED |