Permit: T00EL02477

Parcel: 106051500


Addresses:

527 W SIMMONS RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/16/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/14/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0935*
NO WORK PROGRESS A REFEE HAS BEEN ASSESSED
11/09/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0220*
11/09/00 PROPER (ACCEPTABLE) GROUNDING OF THE SERVICE EQUIPMENT REQUIRES BONDING OF THE COLD WATER SERVICE RISER GAS PIPING (IF GAS IS PIPED TO THE UNIT) AND TO TWO GROUND RODS WHICH ARE SET 6' APART. LEAVE ALL POINTS OF ATTACHMENT OF THE GROUND WIRE EXPOSED FOR INSPECTION. LEAVE THE HOUSE UNLOCKED SO THAT WE MAY ALSO INSPECT THE GROUNDING CONNECTION AT ANY SUB- PANEL INSIDE