Permit: T00EL02460

Parcel: 140291300


Addresses:

3806 E KINISHBA DR

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
12/11/2000 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
OK TO CLEAR
12/07/2000 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999*
SEE NOTE ON 1ST INSPECTION
12/06/2000 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0235*
THE UFER MUST BE TERMINATED AT THE NEUTRAL/GROUND BUSS BAR THEN BONDED TO THE CAN ONLY IF THE NEUTRAL/ BUSS BAR IS NOT ALREADY BONDED W/A BONDING SCREW OR STRAP. THANKS CORRECT AND RECALL