Inspection Status: Approved
Inspection History: SIGN ELECTRIC
Permit Number - T00EL02435
Inspection Description - SIGN ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/31/2001 | SIGN ELECTRIC | Approved | ||
05/11/2001 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999* 1) NEC 351-8, LIQUID TIGHT FLEXABLE METAL CONDUIT TO BE SECURED WITHIN 12" OF EACH TERMINATION AND AT INTERVALS NO MORE THAN 4 1/2'. 2) NEC 348-13, EMT CONDUIT SHALL BE SECURELY FASTENED WITHIN 3' OF EACH TERMINATION, JUNCTION BOX OR ELEC. 3) NEC ARTICLE 250 LISTS REQUIREMENTS FOR BONDING ALL METAL CABINETS, RACEWAYS AND FIXTURES BASICALLY ANY PIECE OF EQUIPMENT MORE THAN 2" IN ANY DIMENSION NEEDS TO BE BONDED TO GROUND |
|
03/15/2001 | SIGN ELECTRIC | Partial Approval | SEE NOTES UNDER T00CM04402 |