Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK TO CLEAR |
|
| 10/12/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* PANEL MOUNTED TOO HIGH SEE N.E.C. FOR HIGHEST ALLOWABLE BREAKER (MEASURED FORM HIGHEST BREAKER SPACE) CLEAN WATER PIPE WHERE BOND CLAMP ATTACHED CLEAN GAS PIPE WHERE BOND CLAMP ATTACHED EXPOSE GROUNDING ELECTRODES TIE WRAPS NOT ACCEPTABLE FOR ATTACHING GROUNDING ELECTRODE CONDUTOR RISER NEEDS TO BE THREADED INTO HUB PROPERLY TO ASSURE BONDING METER BASE IS RATED 150 AMPS (INSTALL 200 AMP FOR 200 AMP SERVICE) |
|
| 10/09/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0910* KNOCKED ON DOOR, NO ANSWER LOCK UP DOGS |