Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/28/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0215* REINSTALL SERVICE CORRECTLY 1) THE METER LOAD CENTER MUST BE PROPERLY GROUNDED 2) THE SUB FEEDER WIRING TO THE SUB PANEL MUST BE INSTALLED INCONDUIT OR IN CABLE ASSEMBLY SUCH AS A SERVICE ENTRANCE ROMEX 3) THE PANEL NEEDS SOME KIND OF MOUNTING BRACKET SYSTEM TO KEEP IT FIRMLY ON WALL | |
| 02/27/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1) OWNER OCCUPANT DOING WORK ( ROBERT SZILAGY) 2) RE INSTALL SERVICE CORRECTLY 3) SUPPORT BOXES | |
| 12/08/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* INSTALL FRONT GATE LIGHTS OR WIRE NUT AND CAP BOX INSTALL FIXTURE AT FRONT DOOR REMOVE ILLEAGEL WIRING ON ROOF ROMEX TYPE INSTALL COVERS TO METER BOX AND INSTALL DEAD FRONT COVER REMOVE OR CORRECTLY INSTALL BOX BELOW SERVICE REMOVE DOUBLE LUGGING AT 20 AMP CIRCUIT BREAKER REMOVE ORANGE CORD AT J-BOX IN GARAGE AND SEAL HOLE REMOVE ORANGE CORD AT REAR PORCH WEATHER PROOF RECEPTACLE AT REAR PORCH AND INSTALL GFI. THERE IS TOO MANY PROBLEMS IN THIS HOUSE HAVE A LICENSED ELECTRICAL CONTRACTOR GO THUR AND REPLACE ALL RECEPTACLES, SWITCHES REMOVE UNUSED WIRING, INSTALL ALL FIXTURES AND CORRECT ALL ELECTRICAL PROBLEMS IN THIS HOUSE AND CALL BACK FOR ANOTHER INSPECTION PROVIDE NAME OF C-11 LICENSED CONTRACTOR AT NEXT INSPECTION REQUEST. WILL ALSO HAVE TO BE CHECKED FOR SAFETY ON ELECTRICAL INSTALL A SMOKE DETECTOR IN EACH BEDROOM |