Permit: T00EL02314

Parcel: 116060440


Addresses:

1540 N PAVO PL

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/04/2000 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
OK TO CLEAR
09/29/2000 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*
SERVICE IS REQUIRED TO BE ADDRESSED PERMANENTLY NO MARKER
USE ONLY ITE BREAKERS NO G.E.
GAS BOND IS REQUIRED BY ELECTRICAL CODE
TOP RIGHT SIDE OF SERVICE ENCLOSURE NOT SUPPORTED RIGIDLY
IF GROUND RODS TO BE LAYED IN TRENCH THEY MUST BE 30" IN GROUND