Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2000 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 09/26/2000 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection 0000* NEED TO COMPLETED ROOF JACK RISER CONDUCTORS 3/0 CU. OR 4/0 AG. GROUND RODS X 2 6' APART PERMENENT ADDRESS LABEL STRAP CONDUIT. CHASE NIPPLE NOT ALLOWED MUST BE THREADED NIPPLE CALL WHEN READY TO INSPECT NEED GROUND BUSHING ON 1/2" CONDUIT |