Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/06/2000 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000* | |
| 10/03/2000 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999* SEAL TIGHT E.M.T. TRANISITION ILLEGAL USING EMT CONNECTOR TAPPING #14 WIRE IS ILLEGAL INSTALL PROPER COLORED CONDUTOR FOR POOL MOTOR CIRCUIT N.M. CONNECTOR IS NOT APPROVED FOR LB PANEL CONNECTION INSTALL NEW GFCI BREAKER FOR POOL LIGHT INSTALL EQUIP GROUND FOR POOL PUMP AND LIGHT CIRCUIT PER N.E.C. USE PROPER SIZED STRAP FOR RISER 4 SQ BOX IS OVERFILLED BOND BOTH ENDS OF CONDUIT SLEEVE PER N.E.C. FOR GROUNDING ELECTRODE CONDUTOR INSTALL #4 WATER BOND PER N.E.C. |