Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/24/2001 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection 0000* NOT READY | |
| 03/14/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* 1) GROUNDING ELECTRODE SYSTEM TO BE CONTINOUS FROM SERVICE TO BOTH GROUND RODS 2) SCRAPE PAINT UNDER GAS BOND 3) NEED GUY BACK BRACE ABOVE ROOF ON RISER 4) BOND WIRE NOT TO BE UNDER CLAMP 5) STRAP CONDUIT CORRECTLY |
|
| 02/22/2001 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245* 1) GROUND GAS AND WATER LINE 2) INSTALL PERMANENT ADDRESS LABEL ON SERVICE NO INK 3) OWNER/OCCUPANT DOING WORK |