Inspection History Details
Inspection Status: Denied
Inspection History: SIGN ELECTRIC
Permit Number - T00EL02261
Inspection Description - SIGN ELECTRIC
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/27/2000 | SIGN ELECTRIC | Denied | IVRS - Inspection 0999* ITEMS NOT REPAIRED OR CORRECTED REE FEE TO BE ISSUED IF NOT CORRECTED NEXT TIME |
|
10/23/2000 | SIGN ELECTRIC | Denied | 10/23/00 3 PHASE CIRCUIT BREAKER AT OWNER PANEL STILL 60 S FEEDS #8 WIRE (40A) WILL CHECK WITH SUPPLIER ON TRANSFORMER TAKING 277 VOLTS YOU MAY BE OK ON THIS I WILL LET YOU KNOW NEUTRAL ON SECONDARY OF TRANSFORMER TO BE TIED TO GROUND WIRE FROM GROUND ROD ALSO 10/23/00 NEW VIOLATION AT ENTRY OF #4 BE INTO J-BOX MUST BE EFFECTIVELY SEALED TO MUSCH OPEN SPACE FOR #4 BC ENTRY |
|
10/13/2000 | SIGN ELECTRIC | Denied | PROBLEM A 3 PHASE CIRCUIT BREAKER FEEDS #8 WIRE (40 AMP) TO J-BOX SHOULD BE A 20A CIRCUIT BREAKER PER CODE #10 WIRE ATTACHED TO #8 REDUCING AMPACITY TO 30A TRANSFORMER DOES NOT APPEAR TO ACCEPT 277 VOLTS ONLY 240 V OR 480 V ON PRIMARY TRANSFORMER PROVIDES A SEPERATELY DEPRIVED SYSTEM NEC 250-20 D REQUIRES A GOUND SYSTEM AT LEAST A #8 TO ONE GROUND ROD THE SECONDARY SIDE OF THE TRANSFORMER HAS TO HAVE A FUSED DISCONNECT OR CIRCUIT BREAKER TO PROTECT SECONDARY CONDUCTORS 3/4" RIGID CONDUIT REQUIRES A FITTING WHERE THEY ENTERY AT J-BOXES |
|
10/10/2000 | SIGN ELECTRIC | Denied | IVRS - Inspection 0950* ELECTRICAL TERMINATIONS TO BE MADE AT BOTH J-BOXES HAS SIGN BEEN SHOP INSPECTED IF NOT WOULD LIKE TO SEE INTERIOR |
|
10/06/2000 | SIGN ELECTRIC | Denied | IVRS - Inspection 0925* NO PLANS, PERMIT ON SITE |