Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T00EL02261

Parcel: 127090080


Addresses:

6015 E BROADWAY BL


Inspection Status: Denied

Inspection History: SIGN ELECTRIC

Permit Number - T00EL02261

Inspection Description - SIGN ELECTRIC

Inspection Status - Denied

Date Description Inspector Results Comments
10/27/2000 SIGN ELECTRIC Denied IVRS - Inspection 0999*
ITEMS NOT REPAIRED OR CORRECTED REE FEE TO BE ISSUED IF NOT CORRECTED NEXT TIME
10/23/2000 SIGN ELECTRIC Denied 10/23/00 3 PHASE CIRCUIT BREAKER AT OWNER PANEL STILL 60 S FEEDS #8 WIRE (40A)
WILL CHECK WITH SUPPLIER ON TRANSFORMER TAKING 277 VOLTS YOU MAY BE OK ON THIS I WILL LET YOU KNOW
NEUTRAL ON SECONDARY OF TRANSFORMER TO BE TIED TO GROUND WIRE FROM GROUND ROD ALSO
10/23/00 NEW VIOLATION AT ENTRY OF #4 BE INTO J-BOX MUST BE EFFECTIVELY SEALED TO MUSCH OPEN SPACE FOR #4 BC ENTRY
10/13/2000 SIGN ELECTRIC Denied PROBLEM A 3 PHASE CIRCUIT BREAKER FEEDS #8 WIRE (40 AMP) TO J-BOX SHOULD BE A 20A CIRCUIT BREAKER PER CODE
#10 WIRE ATTACHED TO #8 REDUCING AMPACITY TO 30A
TRANSFORMER DOES NOT APPEAR TO ACCEPT 277 VOLTS ONLY 240 V OR 480 V ON PRIMARY
TRANSFORMER PROVIDES A SEPERATELY DEPRIVED SYSTEM NEC 250-20 D REQUIRES A GOUND SYSTEM AT LEAST A #8 TO ONE GROUND ROD
THE SECONDARY SIDE OF THE TRANSFORMER HAS TO HAVE A FUSED DISCONNECT OR CIRCUIT BREAKER TO PROTECT SECONDARY CONDUCTORS
3/4" RIGID CONDUIT REQUIRES A FITTING WHERE THEY ENTERY AT J-BOXES
10/10/2000 SIGN ELECTRIC Denied IVRS - Inspection 0950*
ELECTRICAL TERMINATIONS TO BE MADE AT BOTH J-BOXES
HAS SIGN BEEN SHOP INSPECTED IF NOT WOULD LIKE TO SEE INTERIOR
10/06/2000 SIGN ELECTRIC Denied IVRS - Inspection 0925*
NO PLANS, PERMIT ON SITE