Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/29/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 09/26/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0920* NO ONE IN 2601 (PER NOTE ON DOOR TO LET ME IN) WILL NEED TO ENTER RECALL INSPECTION NEED NAME OF LICENSED CONTRACTOR NEED 1/4" HARDWARE FOR SERVICES |
|
| 09/14/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* GROUNDED RECEPTACLE ON UNGROUNDED SYSTEM MISSING FACE PLATES EXPOSED ROMEX WIRE PULLING ELBOW NOT ACCESSABLE TIGHTEN CONDUIT FITTINGS SECURE SERVICE TO WALL STRAP CONDUIT WITHIN 3" NEED GROUNDING ELETRODE SYSTEM INSTALLED ALL SERVICES CORECTLY BOND SERVICES STRAP RISERS NEED LICENSED L-11 CONTRACTOR |