Inspection History Details
Inspection Status: Closed
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/07/2008 | ELECTRIC - RECONNECT | Closed | ||
| 02/13/2001 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999* 1) NEED CONTRACTOR LETTER ON LETTER HEAD STATING THAT HE OR SHE IS DOING WORK AND IS RESPONSIBLE FOR THE ELEC. REPAIR/INSTALLATION. 2) NEED TO SEE 2ND GROUND ROD AT END OF GARAGE. 3) GENERAL PURPOSE SHOP RECEPTICAL REQUIRE GFCI PROTECTION AND BOXES MUST BE FLUSHED OUT! 4) CONDUIT WILL BE REQUIRED FOR PHYSICAL PROTECTION BELOW 8' A.F.F. 5) NEED ACCESS TO ALL INTERIOR. 6) FINAL RECONNECT SUBJECT TO MINIMUM HOUSING DETERMINATION OF STRUCTURE 7) NEED CONTRACTOR VERIFICATION THAT REAR STRUCTURES ARE ELECTRICALLY ISOLATED. |
|
| 01/29/2001 | ELECTRIC - RECONNECT | Partial Approval | NEED COMPANY LETTER HEAD OF LICENSED C-11 CONTRACTOR STATING THAT HE/SHE HAS DONE WORK AT THIS ADDRES. MUST CALL MINIMUM HOUSING/SAFETY DEPARTMENT REAR STRUCTURE FALLING NEED PROPER GROUNDING SEE #4 (OLD) |
|
| 09/22/2000 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999* 1. ADDRESS METER 2. NEED K.O. SEAL AT METER 3. REPLACE MAIN BREAKER WIRE. WIRE IS STRESSED, WIRE BOND RADUIS ,ETC 4. NEED PANEL BOARD IN GARAGE, RPOPERLY TURMINATE, GROUNDING ELECTRODE SYSTEM 5. NEED EMT SLEEVE BELOW 8FT 6. REMOVE ALL INTERMINATED WIRE OR UNUSED WIRE, NEED LICENSED CONTRACTOR 7. WILL NEED FINAL APPROVAL FROM SAFETY DEPARTMENT. REAR STRUCTURE FALLING |