Permit: T00EL02190

Parcel: 138111510


Addresses:

33 E WALKER PL

Inspection Status: Closed

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
04/07/2008 ELECTRIC - RECONNECT Closed
02/13/2001 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999* 1) NEED CONTRACTOR LETTER ON LETTER HEAD STATING THAT HE OR SHE IS DOING WORK AND IS RESPONSIBLE FOR THE ELEC. REPAIR/INSTALLATION. 2) NEED TO SEE 2ND GROUND ROD AT END OF GARAGE. 3) GENERAL PURPOSE SHOP RECEPTICAL REQUIRE GFCI PROTECTION AND BOXES MUST BE FLUSHED OUT!
4) CONDUIT WILL BE REQUIRED FOR PHYSICAL PROTECTION BELOW 8' A.F.F. 5) NEED ACCESS TO ALL INTERIOR. 6) FINAL RECONNECT SUBJECT TO MINIMUM HOUSING DETERMINATION OF STRUCTURE
7) NEED CONTRACTOR VERIFICATION THAT REAR STRUCTURES ARE ELECTRICALLY ISOLATED.
01/29/2001 ELECTRIC - RECONNECT Partial Approval NEED COMPANY LETTER HEAD OF LICENSED C-11
CONTRACTOR STATING THAT HE/SHE HAS DONE WORK AT THIS ADDRES.
MUST CALL MINIMUM HOUSING/SAFETY DEPARTMENT REAR STRUCTURE FALLING
NEED PROPER GROUNDING SEE #4 (OLD)
09/22/2000 ELECTRIC - RECONNECT Denied IVRS - Inspection 0999*
1. ADDRESS METER
2. NEED K.O. SEAL AT METER
3. REPLACE MAIN BREAKER WIRE. WIRE IS STRESSED, WIRE BOND RADUIS ,ETC
4. NEED PANEL BOARD IN GARAGE, RPOPERLY TURMINATE, GROUNDING ELECTRODE SYSTEM
5. NEED EMT SLEEVE BELOW 8FT
6. REMOVE ALL INTERMINATED WIRE OR UNUSED WIRE, NEED LICENSED CONTRACTOR
7. WILL NEED FINAL APPROVAL FROM SAFETY DEPARTMENT. REAR STRUCTURE FALLING