Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/18/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK TO CLEAR SERVICE NOTE HAVE CONTRACTOR BURY GROUND WIRE |
|
| 09/13/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* WHAT IS THE NEW 100 AMP CIRCUIT FOR HAS PERMIT BEEN OBTAINED FOR NEW AC UNIT? GROUND WIRE NEEDS TO BE BURRIED, ITS A TRIP HAZARD IN FRONT OF SERVICE WIRING METHODS FOR 1 1/2" PVC BELOW PANEL ARE INCORRECT PC NOT STRAPPED, GAS INTO PLUMBING FITTING AND PLUMPING PIPE. ONE OF THE CABLES IN PVC APPEARS TO BE ROMEX ROMEX CANNOT BE USED UNDERGROUND CONCENTRIC KNOCK OUTS DAMAGED WHERE GROUNDS ENTER BOTTOM OF SERVICE USE ROMEX CONNECTORS 1999 NEC REQUIRES A BOND BUSHING AND TO GROUND IT TO ENCLOSURE WHEN ENTERING THUR A KO THUR CONECTRICS ( 100 A CIRCUIT BELOW SERVICE) INSULATION ON WIRES TO 50A CB TO BE TAPED WHERE INSULATION CRACKED |