Permit: T00EL02171

Parcel: 135030900


Addresses:

6573 E CALLE DENED


Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Permit Number - T00EL02171

Inspection Description - ELECTRIC - CABLE DROP

Inspection Status - Approved

Date Description Inspector Results Comments
12/06/2000 ELECTRIC - CABLE DROP Approved IVRS - Inspection 0000*
OK TO CLEAR
10/09/2000 ELECTRIC - CABLE DROP Not ready for Inspection THERE HAS NOT BEEN A RESIDENTIAL CONTRACTOR CONFIRMATION AS REQUESTED CALLED # ABOVE LEFT MESSAGE BUT HAS NOT CALLED BACK
10/05/2000 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999$
09/29/2000 ELECTRIC - CABLE DROP Not ready for Inspection IVRS - Inspection 0000*
09/27/2000 ELECTRIC - CABLE DROP Denied IVRS - Inspection 0999*
SERVICE MOUNTED TOO HIGH (SEE ART 110 FOR HIGHEST ALLOWABLE BREAKER)
T.E.P METER CANT EXCEED 6' 3" ABOVE THE FINISHED GRADE
3. RISER IS NOT SECURED PER N.E.C.
4. DRIVE RODS FLUSH OR BELOW FINISH GRADE
WATER BOND IS TOO SMALL INSTALL GAS BOND PER N.E.C. ART 250
J-BOX IS OVERFILLED SEE ART 370
SECURE GROUNDING ELECTRODE CONDUCTOR TO WALL USING PROPER DAMPS PER 110-3
9. BURY GROUNDING ELECTRODE CONDUCTOR PER 250 N.E.C.
LABEL ADDRESS ON METER BASE PER TEP
NEED C-11 LIC CONTRACTOR TO FINISH JOB CALL 791-5550 X136 TO LET US KNOW WHO THE LIC CONTRACTOR IS PANEL LOCKED