Inspection History: ELECTRIC - CABLE DROP
Permit Number - T00EL02171
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/06/2000 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000* OK TO CLEAR |
|
10/09/2000 | ELECTRIC - CABLE DROP | Not ready for Inspection | THERE HAS NOT BEEN A RESIDENTIAL CONTRACTOR CONFIRMATION AS REQUESTED CALLED # ABOVE LEFT MESSAGE BUT HAS NOT CALLED BACK | |
10/05/2000 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999$ | |
09/29/2000 | ELECTRIC - CABLE DROP | Not ready for Inspection | IVRS - Inspection 0000* | |
09/27/2000 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999* SERVICE MOUNTED TOO HIGH (SEE ART 110 FOR HIGHEST ALLOWABLE BREAKER) T.E.P METER CANT EXCEED 6' 3" ABOVE THE FINISHED GRADE 3. RISER IS NOT SECURED PER N.E.C. 4. DRIVE RODS FLUSH OR BELOW FINISH GRADE WATER BOND IS TOO SMALL INSTALL GAS BOND PER N.E.C. ART 250 J-BOX IS OVERFILLED SEE ART 370 SECURE GROUNDING ELECTRODE CONDUCTOR TO WALL USING PROPER DAMPS PER 110-3 9. BURY GROUNDING ELECTRODE CONDUCTOR PER 250 N.E.C. LABEL ADDRESS ON METER BASE PER TEP NEED C-11 LIC CONTRACTOR TO FINISH JOB CALL 791-5550 X136 TO LET US KNOW WHO THE LIC CONTRACTOR IS PANEL LOCKED |