Permit: T00EL02158

Parcel: 121060890


Addresses:

5649 E MABEL ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/19/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
OK TO CLEAR
09/18/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0920*
KNOCKED ON DOOR NO ANSWER
ID CIRCUIT BREAKERS
IMPROPER USE OF 30 AMP BREAKERS, FOR USE FOR A 240 V CIRCUIT, MUST BE 2 P BREAKER DESIGNED AND APPROVED BY U.L. FOR PURPOSE. NOT 30 AMP TWINS.
COULD NOT ACCESS BACK YARD DUE TO DOG
COULD NOT VERIFY GROUND RODS, WATRER BOND, GAS BOND