Inspection History Details
Inspection Status: Approved
Inspection History: SIGN SHOP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/16/2000 | SIGN SHOP | Approved | IVRS - Inspection 0000* NOTES MANUFACTURES OF BREAKERS AND PANEL MUST BE SAME WRAP RISER, 10 MIL TAPE FOR CORROSION PROTECTION AT EARTH, GROUND ROD BENT OVER SHOULD BE LAYING FLAT AT LEAST 2' DEEP IN TRENCH PLUG HOLE AT BOTTOM OF BREAKER PANEL BOND WATER PIPING SYSTEM AT SERVICE ENTRY OR 5' FROM POINT OF ENTRY CHASE NIPPLE NOT APPROVED WIRING METHOD IN 8X8 W/P J-BOX (LB) USE CLOSE NIPPLE CAP OFF ANY UN-USED OR ABANDONED CONDUCTORS IN 8X8 J-BOX |