Permit: T00EL02123

Parcel: 12701008A


Addresses:

5205 E BROADWAY BL


Inspection Status: Approved

Inspection History: SIGN SHOP

Permit Number - T00EL02123

Inspection Description - SIGN SHOP

Inspection Status - Approved

Date Description Inspector Results Comments
10/16/2000 SIGN SHOP Approved IVRS - Inspection 0000*
NOTES
MANUFACTURES OF BREAKERS AND PANEL MUST BE SAME
WRAP RISER, 10 MIL TAPE FOR CORROSION PROTECTION AT EARTH,
GROUND ROD BENT OVER SHOULD BE LAYING FLAT AT LEAST 2' DEEP IN TRENCH
PLUG HOLE AT BOTTOM OF BREAKER PANEL
BOND WATER PIPING SYSTEM AT SERVICE
ENTRY OR 5' FROM POINT OF ENTRY
CHASE NIPPLE NOT APPROVED WIRING METHOD IN 8X8 W/P J-BOX (LB) USE CLOSE NIPPLE
CAP OFF ANY UN-USED OR ABANDONED CONDUCTORS IN 8X8 J-BOX