Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2001 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 04/09/2001 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* 1) BOND WATER AND GAS PIPING. 2) CHASE NIPPLE NOT ALLOWED, MUST BE CLOSE NIPPLE WITH LOCKNUTS BOTH ENDS. 3) CHASE NIPPLE PENETRATION NEEDS TO BE BEHIND DEAD FRONT OF PANEL. 4) GROUND WIRE SHOULD BE BELOW GRADE 5) USE AT LEAST 1/4" SCREWS TO SUPPORT RISER CONDUIT |