Permit: T00EL02081

Parcel: 12112113A


Addresses:

1231 N BEVERLY AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/17/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
04/09/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0245* 1) BOND WATER AND GAS PIPING. 2) CHASE NIPPLE NOT ALLOWED, MUST BE CLOSE NIPPLE WITH LOCKNUTS BOTH ENDS.
3) CHASE NIPPLE PENETRATION NEEDS TO BE BEHIND DEAD FRONT OF PANEL. 4) GROUND WIRE SHOULD BE BELOW GRADE 5) USE AT LEAST 1/4" SCREWS TO SUPPORT RISER CONDUIT