Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK TO CLEAR OK CABLE DROP |
|
| 09/11/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* PROTECT U.G. CIRCUITS PER N.E.C. (TO THE PROPER DEPTH GAS BOND STILL NOT INSTALLED PLEASE CORRECT ALL ITEMS PER N.E.C. TO AVOID A REINSPECTION FEE |
|
| 08/31/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* INSTALL GAS BOND PROTECT U.G. BRANCH CIRCUITS PER NEC ID CIRUCITS AT SERVICE PANEL PER NEC INSTALL BONDING BUSHING ON 2 1/2" RISER INSTALL WEATHER PROOF COVER AT GFI RECEPTACLE NEATLY LABEL ADDRESS IN FUTURE OR USE METAL TAG PER ART 110 WORKMANSHIP |