Permit: T00EL02064

Parcel: 122154250


Addresses:

3314 E LINDEN ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
09/27/2000 ELECTRIC - SERVICE UPGRADE Approved
09/26/2000 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*
OK TO CLEAR
CALL FOR RE-INSPECTION AFTER SMOKE DETECTORS ARE INSTALLED
09/01/2000 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*
NEED WEATHER PROOF FITTING AT TOP OF PANEL
INSTALL GROUNDING ELECTRODE SYSTEM
SECURE CONDUCTORS IN PANEL
NEED EQUIPMENT GROUNDING CONDUCTOR TO SUB PANEL
CAN NOT LOCATE JUNCTION BOX FOR SUB PANEL
NEED PERMIT FOR WORK UNDER PROGRESS INTERIOR OF HOUSE INVESTIGATIVE FEED DUE BEFORE REINSPECTION 'VERIFY LICENSED ELECTRICAL CONTRACTOR