Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T00EL02050
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/04/2000 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection 0000* OK TO CLEAR CABLE DROP AND FINAL |
|
09/27/2000 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999* PERMANENTLY ATTACH ADDRESS TAG TO PEDASTAL PROPERLY TERMINATE GROUNDING ELECTRODE CONDUCTOR TO GROUND ROD AT ACORNS (BOTH) INSTALL IRRIGATION CONTROLLER INSTALL PROPER CIRCUIT BREAKER (SEE LABEL INFO ON COVER) NEED TO BE AT LEAST 36" AWAY FROM TELEPHONE PEDASTAL PER ART 110 |
|
09/21/2000 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999* PEDISTAL REQUIRES 3' OF CLEARANCE IN FRONT OF IT PERMANENTLY LABEL ADDRESS AND USE OF SERVICE IRRIGATION SERVICE GOUND WIRE FROM ELECTRODES NOT CONNECTED TO NEUTRAL CONNECTION TO LOAD REQUIRED WESTING HOUSE BR BREAKER NOT APPROVED FOR THIS PEDISTAL |