Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/24/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
| 11/17/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* DID NOT COMPLY WITH PREVIOUS WRITE-UP FOR GROUNDING TYPE BUSHINGS AT SERVICE 250-94 NEC REQUIRE BOND BUSHINGS BOTH ENDS OF OFFSET NIPPLES BEWTEEN METER BASE AND DISCONNECT SWITCHES |
|
| 11/14/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0235* PLEASE ISOLATE THE GROUND AND NEUTRAL BARS AT THE SUB PANELS BY REMOVING THE BAR STRAP AT THE BOTTOM |
|
| 11/01/2000 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* GROUND BUSHING REQUIRED AT SERVICE 250-94 N.E.C. OK CABLE DROP OK TO CLEAR |