Permit: T00EL02018

Parcel: 12106243B


Addresses:

5620 E PIMA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/24/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
11/17/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
DID NOT COMPLY WITH PREVIOUS WRITE-UP FOR GROUNDING TYPE BUSHINGS AT SERVICE
250-94 NEC
REQUIRE BOND BUSHINGS BOTH ENDS OF OFFSET NIPPLES BEWTEEN METER BASE AND DISCONNECT SWITCHES
11/14/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0235*
PLEASE ISOLATE THE GROUND AND NEUTRAL BARS AT THE SUB PANELS BY REMOVING THE BAR STRAP AT THE BOTTOM
11/01/2000 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*
GROUND BUSHING REQUIRED AT SERVICE 250-94 N.E.C. OK CABLE DROP
OK TO CLEAR