Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T00EL01989
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/26/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK TO CLEAR |
|
09/22/2000 | ELECTRIC - FINAL | Partial Approval | NEED BOND BUSHING AT SQUARE 'D' PANEL TIGHTEN FITTINGS AT SAME PANEL LARGER THAN #8 TO BE STRADED WIRE-310-3 EXPOSED CONDUCTORS SOUTH SIDE |
|
08/24/2000 | ELECTRIC - FINAL | Denied | ||
08/18/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* EXPOSED CONTORS SOUTHSIDE WP IN CENTER EXPOSED ROMEX IN ARCH USE APPROVE R CONDUIT BOXES AND COVER FOR RECEPTACLES ON PROCH NEED BALLAST COVER FOR FIXTURE MISSING COVER PLATES NEED APPROVED PANEL COVER PER MANUFACTURE STRAP CONDUIT PER CODE SEAL OR REMOVE USUSED FITTINGS AT PANEL NEED MAIN BONDING JUMPER NEED GROUNDING ELECTRODE CONDUTOR TO SUB PANEL MISSING KO SEALS NEED LICENSED CONTRACTOR NEED PERMIT FOR WORK ON INTERIOR WALLS NEED TO SEE ELECTRIC |
|
08/17/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* NOTIFY TEP TO RECONNECT NEUTRAL CONDUCTOR AT SERVICE DROP PLUG KO HOLES ON SERVICE DISC SWITCH REPAIR BACK OUTSIDE LIGHT FIXTURE ROMEX WIRING DOWN SOUTH WALL WITH CORD CONNECTOR NOT APPROVED MUST BE IN CONDUIT LEAVE KEY OR MEET INSPECTOR FOR ACCESS TO INSIDE BLDG |