Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* ALL ITEMS CORRECTED FROM PREVIOUS WRITE UP |
|
| 10/04/2000 | ELECTRIC - FINAL | Denied | 10/04/00 LARGER TRANSFORMER 45 K VA GROUND WIRES AND NEUTRALS NOT TIED DOWN IN LUG PULLED RIGHT OFF DO NOT USE A NEUTRAL COLORED CONDUTOR FOR GROUND ELECTRODE CONDUCTOR ON TRANSFORMERS MUST BE GREEN 30 KVA TRANS GROUNDS NOT ATTACHED TIGHTLY PULL RIGHT OFF REQUIRE LISTING ON EQUIPMENT OWNER TO CHECK CORD CAPS ON CORDS CONNECTED TO 60 A PNL |