Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/02/2000 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* OK TO CLEAR |
|
| 10/30/2000 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0230* THE INSTALLATION OF THE NEW ELECTRIC SERVICE REQUIRES THAT TWO (2) GROUND RODS 5/8 X8' BE DRIVEN TO TWO INCHES BELOW THE GROUND LEVEL AND BE SET 6' APART. A #6 SOILD GROUND SIRE (COPPER) MUST BE ATTACHED TO THE RODS AND RUN INTO THE PANEL AND CONNECTED TO THE GROUND NEUTRAL BUSS BAR |
|
| 08/16/2000 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0920* NO ANSWER OK TO ENTER PLEASE RECALL |