Permit: T00EL01946

Parcel: 120091240


Addresses:

401 E MICHIGAN DR

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/24/2001 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
06/21/2001 ELECTRIC - SERVICE UPGRADE Partial Approval OK TEMP POWER
04/27/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*
01/02/2001 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*
UNDERGROUND NEEDS TO BE 18" MIN DEPTH TO TOP OF CONDUIT
MUST USE SCHEDULE 80 PVC FOR ABOVE GROUND EXTENSIONS RECALL THIS INSPECTION A RE FEE IS DUE BEFORE THE NEXT INSPECTION
12/28/2000 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0930$
NEED LETTER FROM LICENSED C-11 CONTRACTOR FOR FILES PROR TO INSPECTION ON GOING INSPECTION
11/13/2000 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*
LICENSED CONTRACTOR DOING SERVICE AND A/C CIRCUIT IS MR. ELECTRIC
I NEED A LICENSED CONTRACTOR TO FINISH THE RE FEED TO THE EXISTING SERVICE AREA
WIRING METHODS USED TO REFEED EXISTING IS NOT APPROVED WORKMANSHIP STANDARS AND OTHER CODE ISSUES VIOLATED
NEED A/C PERMIT
NEED FEEDER CIRCUIT PERMIT
CALL 791-5550 EXT 136 AND LEAVE NAME AND NUMBER OF REQUIRED C-11 CONTRACTOR. A/LETTER W/ COMPANY LETTER HEAD WILL ALSO BE REQUIRED
10/26/2000 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*
STRAP GROUND WIRE FIRMLY TO WALL
INSTALL A WATER BOND
INSTALL A GAS BOND
NEED TO SEE START OF WIRING METHOD THAT WILL BE USED TO RE FEED EXISTING CIRCUITS
PLEASE COMPLETE THEIR AS FOR AS POSSIBLE
CALL FOR ELECTRICAL FINAL ON THE A/C PERMIT