Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T00EL01930

Parcel: 11903226E


Addresses:

3140 S 10TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/18/2000 ELECTRIC - FINAL Approved 10/18/00 OK TO CLEAR RECON
10/16/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
PANEL NEEDS A DEAD FRONT COVER
REMOVE 30 A CIRCUIT BREAKER IN PANEL AND USE 20 AMP
REMOVE DOUBLE LUGGING UNDER 30A CB
INSTALL A WIRE NUT PROPERLY ON NEUTRALS IN PANEL ( TOO MUCH WIRE SHOWING)
FRONT PORCH LIGHT IS NOT WEATHER PROOF ITS ON INSIDE FIXTURE
08/11/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
INSTALL A DEAD FRONT COVER IN SERVICE PANEL
SUPPORT 1/2" AND 3/4" CONDUITS GOING UP OUTSIDE PANEL
TAN 1/2" CONDUIT HAS COME OUT OF ELBOW
COVER HOLE AT 4" SQUARE J-BOX NEXT TO PANEL OUTSIDE
FRONT PORCH LIGHT TO HAVE J-BOX NEXT TO PANEL OUTSIDE
FRONT PORCH LIGHT TO HAVE J-BOX BEHIND IT
SW COVER IN LIVING ROOM
INSTALL SMOKE DETECTORS IN BEDROOMS
SHEET ROCK CEILING IN NW BEDROOM AND FINISH
WEST WALL OUTSIDE FOR WASHER TO BE WEATHER PROOF AND CONDUIT HAS BEEN PULED APART CONDUIT ON ROOF LOOSE AND NOT SUPPORTED
DISCONNECT WIRING TO REAR STRUCTURE AND PIPING AT WASHER OUT LGT
WATER LHEATER IS REQUIRED TO BE ENCLOSED
OUTSIDE PORCH LIGHT TO BE REMOUNTED