Permit: T00EL01914

Parcel: 115200610


Addresses:

1919 W WAVERLY ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
11/03/2000 ELECTRIC - SERVICE UPGRADE Approved
10/12/2000 ELECTRIC - SERVICE UPGRADE Partial Approval 10/13/00 OK TO CLEAR
09/11/2000 ELECTRIC - SERVICE UPGRADE Denied BOND GAS
STRAP GROUND WIRE TO WALL
SIZE BONDING JUMPER ACCORDINGLY TO CODE
NEED LOCKNUT AND BOTH REDUCING WASHERS
NEED 2 SUPPORTS ON RISER BELOW ROOF WITH ANCHOR NOT NAILS
SUPPORT1" CONDUIT WITHIN 3' OF FITTINGS AT PANEL
NEED SWIMMING POOL MOVED TO MEET CLEARENCES PER CODE
NEED TO SEE CROSSOVER CONNECTIONS AFTER CLEARANCE
PLEASE LEAVE OLD INSPECTION REPORTS OUTSIDE
09/08/2000 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*
2 SUPPORTS REQUIRED ON RISER BELOW ROOF LINE
INSTALL ROOF JACK
ELECTRICAL LINES OVER POOL NEED TO BE 25' ABOVE WATER OR MOVE POOL
USE ROMEX CONNECTION ON GROUND WIRES AT BOTTOM OF SERVICE
NEED TO USE A GROUNDING BUSHING AT ENTRY TO CON ON 1" LB BECAUSE YOU GO THUR CONCENTRICS
USE CORRECT BREAKERS
MUST USE A PERMANENT LABEL ON SERVICE NO PEN
STRAP #4 TO WALL
DRIVE RODS TO BELOW GRADE AND BURY GROUND WIRE