Permit: T00EL01876

Parcel: 133180100


Addresses:

6951 E 1ST ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/17/2000 ELECTRIC - FINAL Approved
08/08/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
CHASE NIPPLE NOT APROVED AT 1/2" LB . IF RW'S ARE USED INSTALL BOND BUSHING
WATER BOND CONDUCTOR MUST BE CONTINUEOUS RUN OF WIRE OR IF SPLICED MUST BE IRREVERSIBLE TYPE (CRIMP OR CADWELD)
GAS PIPING SYSTEM MUST BE BONDED