Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* NEED 2 SUPPORTS ON RISER ABOVE PANEL NEED LOCKNUT ON CHASE NIPPLE FOR L.B. NEED PERMANENT METAL ADDRESS LABEL COMPLETELY LABEL ALL BREAKERS NEED GAS BOND 250-104 USE CORRECT SCREWS TO HOLD DEAD FRONT REPAIR LOOSE NEUTRAL CONNECTION WIRE BURY GROUND WIRE CORRECTLY IDENTIFY HOT CONDUCTORS PLEASE RECALL WHEN READY |