Permit: T00EL01777

Parcel: 128112680


Addresses:

4818 E CECELIA ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
12/04/2000 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
08/22/2000 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*
BOND GAS ON PIPE AFTER METER NOT SUPPLY SIDE
WILL NEED AN APPROVED RAIN TIGHT JUNCTION BOX UPON FINAL
TRANSITION INTO EXISTING WIRE
CONCRETE BLOCK BORDER I FRONT OF SERVICE NOT APPROVED NEED PROPER CLEARANCE
RISER NOT STRAPPED AT TOP PLATE
07/27/2000 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*
1. NEED GAS BOND
2. GROUND ROD TO BE AT LEAST 6' APART
3. NEED PERMANENTMETAL ADDRESS LABEL
4. NEED TO SEE CROSSOVER CONNECTIONS
5. STRAP RISER AT TOP PLATE