Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/04/2000 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* | |
| 08/22/2000 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* BOND GAS ON PIPE AFTER METER NOT SUPPLY SIDE WILL NEED AN APPROVED RAIN TIGHT JUNCTION BOX UPON FINAL TRANSITION INTO EXISTING WIRE CONCRETE BLOCK BORDER I FRONT OF SERVICE NOT APPROVED NEED PROPER CLEARANCE RISER NOT STRAPPED AT TOP PLATE |
|
| 07/27/2000 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* 1. NEED GAS BOND 2. GROUND ROD TO BE AT LEAST 6' APART 3. NEED PERMANENTMETAL ADDRESS LABEL 4. NEED TO SEE CROSSOVER CONNECTIONS 5. STRAP RISER AT TOP PLATE |