Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T00EL01769
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/21/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* JUNCTION ALL EXPOSED WIRING AT CARPORT 2903 AT J-BOX 2901 LABEL ALL SERVICE EQUIP PER T.E.P. SPECIFICATION (METAL TAG) REMOVE SHELVING AND LOWER CABINET IN WAY OF THE REQUIRED WORKING CLEARANCE (2951) PER ART. 110 N.E.C. |