Permit: T00EL01754

Parcel: 122151300


Addresses:

3133 E PIMA ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/06/2000 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
OK TO CLEAR
10/17/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
PERMANENT ADDRESS LABEL REQUIRED
N.E.C. 230-70 B AND CITY OF TUCSON ORDIN #9287
2" OF EXPOSED WIRING BEHIND THE SERVICE PANEL SHALL BE PROTECTED BY MEANS THAN SILICONE CAULK N.E.C. 320-1, 320-14, 90-4
3/4" PLASTIC BUSHING AT TOP OF PANEL NOT APPROVED MUST BE A FITTING APPROVED TO BE WATER TITE
RE-SUPPORT SREVICE, LAG BOLTS ARE PULLING OUT OF BRICK WALL NEC 90-4
07/19/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
NEED PERMANENT ADDRESS TAG
GAS PIPING SYSTEM BOND
SILICONE CAULK NOT AN APPROVED RACEWAY FOR HOUSE FEEDER SLEEVE