Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/06/2000 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK TO CLEAR |
|
| 10/17/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* PERMANENT ADDRESS LABEL REQUIRED N.E.C. 230-70 B AND CITY OF TUCSON ORDIN #9287 2" OF EXPOSED WIRING BEHIND THE SERVICE PANEL SHALL BE PROTECTED BY MEANS THAN SILICONE CAULK N.E.C. 320-1, 320-14, 90-4 3/4" PLASTIC BUSHING AT TOP OF PANEL NOT APPROVED MUST BE A FITTING APPROVED TO BE WATER TITE RE-SUPPORT SREVICE, LAG BOLTS ARE PULLING OUT OF BRICK WALL NEC 90-4 |
|
| 07/19/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* NEED PERMANENT ADDRESS TAG GAS PIPING SYSTEM BOND SILICONE CAULK NOT AN APPROVED RACEWAY FOR HOUSE FEEDER SLEEVE |