Permit: T00EL01732

Parcel: 126090880


Addresses:

201 N COLUMBUS BL

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/12/2000 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
08/31/2000 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*
OK TO CLEAR
2/0 GROUNDING BOND WIRE FOR GAS AND WATER SHOULD BE STRAPPED WITH APPROVED STRAPS, AS BY WATER AND GAS BOND 1/8" TY RAPS NOT AN APPROVED SUPPORTING METHOD
08/24/2000 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*
COULD NOT LOCATE GAS BOND
DOOR LOCKED NO ACCESS TO ROOM WHERE SUB PANEL IS LOCATED
REMOVE COVER ON 400 AMP PANEL BOARD
CONTR NOT ON SITE
08/22/2000 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0245*
BONDING TYPE BUSHINGS REQUIRED ON ALL SERVICE RELATED ENCLOSURES 250-94
BOND GAS PIPING SYSTEM 250-104B
PERMANENT ADDRESS LABEL ON METER BASE
NEED TO INSPECT CONNECTION TO SUB PANEL ROOM LOCKED NO ACCESS