Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/12/2000 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* | |
| 08/31/2000 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection 0000* OK TO CLEAR 2/0 GROUNDING BOND WIRE FOR GAS AND WATER SHOULD BE STRAPPED WITH APPROVED STRAPS, AS BY WATER AND GAS BOND 1/8" TY RAPS NOT AN APPROVED SUPPORTING METHOD |
|
| 08/24/2000 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection 0000* COULD NOT LOCATE GAS BOND DOOR LOCKED NO ACCESS TO ROOM WHERE SUB PANEL IS LOCATED REMOVE COVER ON 400 AMP PANEL BOARD CONTR NOT ON SITE |
|
| 08/22/2000 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245* BONDING TYPE BUSHINGS REQUIRED ON ALL SERVICE RELATED ENCLOSURES 250-94 BOND GAS PIPING SYSTEM 250-104B PERMANENT ADDRESS LABEL ON METER BASE NEED TO INSPECT CONNECTION TO SUB PANEL ROOM LOCKED NO ACCESS |