Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2000 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999* 1. PERMANENT ADDRESS REQUIRED AT SERVICE 2. INSTALL AN APPROVED JUNCTION BOX IN CLOSET EG A 12X12 JUNCTION BOX AND PROPERLY TERMINATE CONDUTORS WITH CONNECTION 3. WILL NEED AN APPROVED PLAN AND APPROVED INSPECTION FOR CARPORT INCLUDING BUILD ELECTRICAL ANY MECHANICAL AND PLUMBING 4. WILL NEED A BUSHING FOR THROUGH WIRING BEHIND SERVICE 5. NEED INTERIOR WATER AND GAS BOND 6. POINT OF ATTACHEMTN TO BE A MINIMUM OF 12 FT ABOVE GRADE |