| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2000 | ELECTRIC - FINAL | Approved | ||
| 07/13/2000 | ELECTRIC - FINAL | Denied | 1. INSTALL GROUNDING ELECTRODE SYSTEM PER MINIMUM REQUIREMENTS OF THE NATIONAL ELEC CODE 250-52 2. BOND GAS TO SERVICE PER 250-104 3. BOND WATER TO SERVICE PER 250-104 4. BONDING BUSHING REQUIRED AT OFF SET NIPPLE TO BOND OFFSET NIPPLE PER 250-94 (STARNDARD LOCKNUTS SHALL NOT BE THE SOLE MEANS OF BONDING THE NIPPLE) 5. CONNECT GROUNDING ELECTRODE SYSTEMS TOGETHER FROM OTHER SERVICE 6. ID SERVICES #1 & 2 |