Permit: T00EL01635

Parcel: 106050470


Addresses:

462 W SIMMONS RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/25/2000 ELECTRIC - FINAL Approved
07/21/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1. STRAP RISER WITHIN 3' OF PANEL
2. STRAP GROUNDING ELECTRODE CONDUCTOR
3. NEED WATER AND GAS BONDS 250-104
4. NEED TO SEE CROSS OVER CONNECTIONS
5. NEED LICENSED ELECTRICAL CONTRACTOR