Permit: T00EL01591

Parcel: 13624228C

Inspection Status: Correction Required

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/26/2000 ELECTRIC - FINAL Correction Required ADDTL COMMS - 1. PUT AN ADDRESS ON SERVICE WITH BLDG # AND OWNERS 2. RUN CONDUIT AND CONDUCTORS TO CT CAN 3. ISOLATE NEUTRALS AND GRUOND AT SUB PNL 4. NEED A GROUND BUSHING AT OFF SET NIPPLE ON DISCONNECT SIDE (A FAULT WILL TRAVEL EITHER WAY)
06/26/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*