Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2000 | ELECTRIC - FINAL | Denied | SERVICE NEEDS TO BE RELOCATED GAS METERS CANNOT BE IN THE REQUIRED WORKING CLEARANCE AREA ALSO SOUTHWEST GAS DOESN'T WANT ELC, PANELS WITHIN 3' OF THEIR GAS METERS |
|
| 08/04/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* NOTE NEED 2ND METER LOOP PURCHASED PRIOR TO ELEC CLEARANCE RELOCATE SERVICE SEE ART 110 FOR REQUIRED WORKING CLEARNACE INSTALL GROUNDING ELECTRODE SYSTEM SCREWS MISSING ON DEAD FRONT COVER CLEAN WATER AND GAS PIPING WHERE BONDING CLAMPS ATTACHED INSTALL I.M.C. INTO HUB FARTHER TO ASSURE PROPER MECHANICAL STRENGTH LABEL ADDRESSES PER TEP |