Permit: T00EL01558

Parcel: 132110610

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/10/2000 ELECTRIC - FINAL Denied SERVICE NEEDS TO BE RELOCATED
GAS METERS CANNOT BE IN THE REQUIRED WORKING CLEARANCE AREA
ALSO SOUTHWEST GAS DOESN'T WANT ELC, PANELS WITHIN 3' OF THEIR GAS METERS
08/04/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
NOTE NEED 2ND METER LOOP PURCHASED PRIOR TO ELEC CLEARANCE
RELOCATE SERVICE SEE ART 110 FOR REQUIRED WORKING CLEARNACE
INSTALL GROUNDING ELECTRODE SYSTEM
SCREWS MISSING ON DEAD FRONT COVER CLEAN WATER AND GAS PIPING WHERE BONDING CLAMPS ATTACHED INSTALL I.M.C. INTO HUB FARTHER TO ASSURE PROPER MECHANICAL STRENGTH
LABEL ADDRESSES PER TEP