Permit: T00EL01520

Parcel: 116124370

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/26/2001 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
OK TO CLEAR 3 &4 #1&2 RECONNECT ALREADY RECONNECTED
01/21/2001 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
NO MESSAGE ON IVR NOTED THAT THERE WAS A CALL FOR ONE
#4 USE APPROVED WIRING METHOD FOR HEATER
#3 USE APPROVED WIRING METHOD FOR HEATER
COMPLETE PREVIOUS INSPECTION REPORTS
10/27/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
10/24/2000 ELECTRIC - FINAL Denied 10/24/00 DISCONNECT #3 HAS A 1" OPEN HOLE AT BOTTOM SEAL IT OFF
BASE BOADR HEATER NEED TO HAVE CORD REMOVED AND HARDWIRED ALL THE WAY INTO J-BOX WITH #12 WIRE ALL THE WAY
08/24/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
07/19/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1. NEED HEATING
2. SUPPORT CONDUTORS AT SOB PANEL #4
3. COVER NEED TO BE WEATHER PROOF 410-57
07/14/2000 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1. NEED ATTACHED HEATING UNIT
2. BOXES OUTSIDE NEED TO BE WEATHER PROOF
NEED ATTACHED HEATING UNIT
3. NEED ATTACHED HEATING UNIT
4. NEED ATTACHED HEATING UNIT SUPPORT CABLES AT SUB PANEL NEED CORRECT CONNECTIONS FOR
GROUNDING ELECTRODE CONDUTORS BOND ALL GAS
SERVICES NOT JUST 1 UNIT SUPPORT CONDUCTOR AND CONDUIT FROM SERVICES PROTECT SERVICE CONDUCTORS #2 NEED PERMANENT METAL ADDRESS LABELS