Permit: T00EL01489

Parcel: 12904287A


Addresses:

345 S KINO PW #02


Inspection Status: Denied

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T00EL01489

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Denied

Date Description Inspector Results Comments
08/24/2000 ELECTRIC - INTERMEDIATE Denied
08/22/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
OPEN METER COMPARTMENT ACTUALLY JUST CUT U BOLT OFF AND I'LL OPEN METER BASE FOR INSPECTION SELF TAPPING SCREWS NOT AN ACCEPTED WAY WAY OF BOND BUIDLING STELL
08/17/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*
COULD NOT VERIFY BOND BUSHING ON 4" 1N METER BASE DUE TO TEP SEAL
2 1/2" NOT BONDED WITH BRAID BUSHING IN DISCONNECT COULD NOT VERIFY GAS BOND CONTRACTORS NOT ON SITE
08/16/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0920*
GATES LOCKED
NO ONE AT RECEPTION AREA COULDN'T LOCATE ENTRY OFFICE PERSONNEL FOR ACCESS 7:40 AM
08/11/2000 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection 0000*
08/11/2000 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0999*
BOND RISER EMT CONNECTOR 4" AND BOND EMT NIPPLE 2 1/2" USING BONDING BUSHING OR
BONDING LOCKNUT NO STANDARD
LOCKNUT IS NO LONGER ACCEPTABLE FOR BONDING NIPPLE OR RACEWAY
BOND GAS PIPING
BOND BUILDING STEEL OK UG