Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T00EL01489
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/24/2000 | ELECTRIC - INTERMEDIATE | Denied | ||
08/22/2000 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* OPEN METER COMPARTMENT ACTUALLY JUST CUT U BOLT OFF AND I'LL OPEN METER BASE FOR INSPECTION SELF TAPPING SCREWS NOT AN ACCEPTED WAY WAY OF BOND BUIDLING STELL |
|
08/17/2000 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0245* COULD NOT VERIFY BOND BUSHING ON 4" 1N METER BASE DUE TO TEP SEAL 2 1/2" NOT BONDED WITH BRAID BUSHING IN DISCONNECT COULD NOT VERIFY GAS BOND CONTRACTORS NOT ON SITE |
|
08/16/2000 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0920* GATES LOCKED NO ONE AT RECEPTION AREA COULDN'T LOCATE ENTRY OFFICE PERSONNEL FOR ACCESS 7:40 AM |
|
08/11/2000 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection 0000* | |
08/11/2000 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection 0999* BOND RISER EMT CONNECTOR 4" AND BOND EMT NIPPLE 2 1/2" USING BONDING BUSHING OR BONDING LOCKNUT NO STANDARD LOCKNUT IS NO LONGER ACCEPTABLE FOR BONDING NIPPLE OR RACEWAY BOND GAS PIPING BOND BUILDING STEEL OK UG |