Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 06/15/2000 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
|
| 06/12/2000 |
ELECTRIC - SERVICE UPGRADE |
|
Correction Required |
ADDTL COMMS - 1. ISOLATE NEUTRAL FROM GROUNDING CONDUTORS AT SUB PANEL AND BOND PANEL ENCLOSURE TO GROUNDING BUS BASE 2. INSTALL GROUNDING ELECTRODE SYSTEM AT SERVICE 3. BOND GAS 4. BOND WATER AT SERVICE 5. INSTALL PROPER BREAKER FOR SUB PANEL FEED (NOTE MAX. BRANCH CIRCUIT IS 100 AMPS PER SQUARE D) SEE LABEL 6. P.V.C. NOT ACCEPTABLE FOR RISER PER N.E.C. 90-4 AND T.E.P. 7. WEATHER HEAD DAMAGED 8. RISER TOO LOW NEED MIN OF 10 FOR T.E.P. POINT OR ATTACHMENT 9. LABEL ADDRESS AT METER BASE 10. A LIC CONTRACTOR IS REQD TO DO THIS PER STATE OF AZ 11. NEED APPROVED PLANS FOR ALL NEW WIRING. |
| 06/12/2000 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999* |