Inspection History Details
Inspection Status: Correction Required
Inspection History: ELECTRIC - FINAL
Permit Number - T00EL01284
Inspection Description - ELECTRIC - FINAL
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/25/2000 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - 1. INSTALL L.B. OR BELL BOX FOR TRANSITION FROM CABLE TO CONDUIT AT A.C. UNIT 2. CLEAN PAINT OFF GAS PIPING WHERE BOND CLAMP IS ATTACHED 3. CLEAN WATER PIPE WHERE CLAMP IS ATTACHED FOR BOND 4. USE ANT: OXIDATION PASTE AT ALUM. SPLICES. | |
05/25/2000 | ELECTRIC - FINAL | Denied | DENIED | |
05/23/2000 | ELECTRIC - FINAL | Correction Required | ADDTL COMMS - NOTES: SPLICES ABOVE BREAKER COMPARTMENT NOT ACCESSABLE MAIN HOUSE WATER SYSTEM NOT BONDED 2 GROUND RODS REQUIRED GAS PIPING SYSTEM NOT BONDED. | |
05/23/2000 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245* |