Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/24/2000 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
|
| 07/14/2000 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 06/12/2000 |
ELECTRIC - SERVICE UPGRADE |
|
Correction Required |
ADDTL COMMS - 1. ISOLATE NEUTRAL FROM GRONDING CONDUCTORS AT NEW SUB PANEL (DRYER) 2. IDENTIFY NEUTRAL CONDUCTOR WHITE AT WEATHERHEAD AND AT METER SECTION 3. BOND GAS AND WATER PIPES TO MAIN ELECTRICAL SERVICE 4. USE 1/4 LAG SCREWS OR EQUAL FOR SECURING THE RISER 5. INSTALL SEPERATE NEUTRAL FOR BRANCH CIRCUIT 6. LABEL ADDRESS AT METER BASE 7. A PERMIT IS REQUIRED FOR THE ADDITION |
| 06/12/2000 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999* |