Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2000 | ELECTRIC - CABLE DROP | Approved | ||
| 07/06/2000 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection 0999* 1. USE CORRECT SINGLE CONDUCTORS TO FEED SUB PANEL (NOT STRIPPED S.E. CABLE) 2. THE SHEET METAL SCREW IS NOT ACCEPTABLE AS A GROUNDING MEANS ALSO BEING USED TO HOLD UP PANEL 3. CANNOT USE OLD SUB PANEL AS JUNCTION BOX RE FIGURE OR USE APPROVED RAUIT RIGIT JUNCTION BOX 4. ISOLATE GROUND AND NEUTRALS 5. SEPERATE CONDUCTORS TO EXIST SERVICE 6.RUN NEUTRALS ALL THE WAY TO SERVICE BRANCH CIRCUIT ORIGINATION 7. ADDRESS SERVICE 8. DOUBLE LUGGING AT RODS |