Permit: T00EL01279

Parcel: 13005292A


Addresses:

2325 S MARTIN AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE RELOCATION

Date Description Inspector Results Comments
08/24/2000 ELECTRIC - SERVICE RELOCATION Approved
06/12/2000 ELECTRIC - SERVICE RELOCATION Correction Required ADDTL COMMS - 1. ISOLATE NEUTRAL FROM GROUNDING CONDUTORS AT NEW SUBPANEL (DRYER) 2. IDENTIFY NEUTRAL CONDUCTOR WHITE AT WEATHERHEAD AND AT METER SECTION 3. BOND GAS AND WATER PIPES TO MAIN ELECTRICAL SERVICE 4. USE 1/4 LAG SCREWS OR EQUAL FOR SECURING THE RISER 5. INSTALL SEPERATE NEUTRAL FOR BRANCH CIRCUITS 6. LABEL ADDRESS AT METER BASE 7. A PERMIT IS REQUIRED FOR THE ADDITION
06/12/2000 ELECTRIC - SERVICE RELOCATION Denied IVRS - Inspection 0999*