Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date |
Description |
Inspector |
Results |
Comments |
| 08/24/2000 |
ELECTRIC - SERVICE RELOCATION |
|
Approved |
|
| 06/12/2000 |
ELECTRIC - SERVICE RELOCATION |
|
Correction Required |
ADDTL COMMS - 1. ISOLATE NEUTRAL FROM GROUNDING CONDUTORS AT NEW SUBPANEL (DRYER) 2. IDENTIFY NEUTRAL CONDUCTOR WHITE AT WEATHERHEAD AND AT METER SECTION 3. BOND GAS AND WATER PIPES TO MAIN ELECTRICAL SERVICE 4. USE 1/4 LAG SCREWS OR EQUAL FOR SECURING THE RISER 5. INSTALL SEPERATE NEUTRAL FOR BRANCH CIRCUITS 6. LABEL ADDRESS AT METER BASE 7. A PERMIT IS REQUIRED FOR THE ADDITION |
| 06/12/2000 |
ELECTRIC - SERVICE RELOCATION |
|
Denied |
IVRS - Inspection 0999* |